6. SUB-FRAME requirements
1. The sub-frame must be capable of supporting the self-weight of the glass elements, wind loads and the resulting loads.
2. The deflection of the sub-frame when the above mentioned loads are applied must not exceed 1/300 of the facade height.
3. Stabilisation of the sub-frame by means of the glass is not allowed.
4. The connection of the glass units to the sub-frame is to follow the fixed- / moving connection principle.
Joint seals
For the inner seal there are pre-formed silicone profiles available. The outer seal (weather-seal) must be carried out using suitable sealing material which is compatible with the secondary seal – DC–3362 HVGER – of the insulating unit. DOW Corning DC 791 is a compatible silicone sealant. The stainless-steel restraining clips in the edge of the glass must be cleaned prior to sealing the joint. The instructions of the sealant manufacturer are to be strictly followed.
Installation
Installation is only to be carried out by professional glaziers who have been trained by ECKELT for this kind of work.
Important installation notes can be downloaded here on the right of the page.